Commission Decision of 9 November 2007 establishing the ecological criteria for the award of the Community eco-label to electrically driven, gas driven or gas absorption heat pumps (notified under document number C(2007) 5492) (Text with EEA relevance) (2007/742/EC)
Grade B
mapped from publisher markup. A grade says how a document's structure was obtained, not how reliable the law is.
Address https://gelex.eu/eli/EU/decision/2007/742@2007-11-09/en
Contents
- Preamble
- ANNEX
- ANNEX ECOLOGICAL CRITERIA
- The aims of the criteria
- Assessment and verification requirements
- Guidance for purchasing an Ecolabelled heat pump — Information fiche for customers —
- Guidance for installing an Ecolabelled heat pump — Information fiche for installers —
- 1. Definitions
- 3. Seasonal performance factor and energy consumption for heating
- 4. Seasonal energy efficiency ratio and energy consumption for cooling
THE COMMISSION OF THE EUROPEAN COMMUNITIES,
Having regard to the Treaty establishing the European Community,
Having regard to Regulation (EC) No 1980/2000 of the European Parliament and of the Council of 17 July 2000 on a revised Community eco-label award scheme, and in particular the second subparagraph of Article 6(1) thereof and the sixth paragraph of point 2 of Annex V thereof,
After consulting the European Union Eco-Labelling Board,
Whereas:
(1) Under Regulation (EC) No 1980/2000, the Community eco-label may be awarded to a product possessing characteristics which enable it to contribute significantly to improvements in relation to key environmental aspects.
(2) Regulation (EC) No 1980/2000 provides that specific eco-label criteria, drawn up on the basis of the criteria drafted by the European Union Eco-Labelling Board, are to be established according to product groups.
(3) The ecological criteria, as well as the related assessment and verification requirements, should be valid for a period of three years.
(4) The measures provided for in this Decision are in accordance with the opinion of the Committee instituted by Article 17 of Regulation (EC) No 1980/2000,
HAS ADOPTED THIS DECISION:
Article 1
The product group electrically driven, gas driven or gas absorption heat pumps shall comprise heat pumps, which can concentrate energy present in the air, ground or water into useful heat for the supply of space heating or the opposite process for space cooling. A heat pump is the device or set of devices as delivered by the manufacturer or importer to the distributor, retailer or installer. This delivery may or may not include the delivery of circulating pumps at the sink or source side, however for calculation of coefficient of performance (COP) values the power consumption of circulating pumps shall always be taken into account, according to the methodology of EN14511:2004 (if the manufacturer cannot provide data, a default value is taken). For gas absorption heat pumps the methodology shall be according to EN12309-2:2000. The product group shall cover only electrically driven, gas driven or gas absorption heat pumps with a maximum heating capacity of 100 kW. The product group electrically driven, gas driven or gas absorption heat pumps shall not cover the following:
(a) heat pumps which can only provide hot water for sanitary use;
(b) heat pumps which can only extract heat from a building and eject it to the air, ground or water thus resulting in space cooling.
Article 2
In order to be awarded the Community eco-label under Regulation (EC) No 1980/2000, a heat pump must fall within the product group electrically driven, gas driven or gas absorption heat pumps and must comply with each of the criteria set out in the Annex to this Decision.
Article 3
For administrative purposes, the code number assigned to the product group electrically driven, gas driven or gas absorption heat pumps shall be 31.
Article 4
The ecological criteria for the product group electrically driven, gas driven or gas absorption heat pumps, as well as the related assessment and verification requirements, shall be valid until 9 November 2010.
Article 5
This Decision is addressed to the Member States.
Done at Brussels, 9 November 2007. For the Commission Stavros Dimas Member of the Commission
ANNEX
ANNEX ECOLOGICAL CRITERIA
The aims of the criteria
These criteria aim to limit the environmental impacts from manufacture, operation and end of life of electrically driven, gas driven or gas absorption heat pumps. They include: The criteria are set at levels that promote the labelling of heat pumps that ensure low environmental impact.
the efficiency of heating and/or heating/cooling of buildings,
reducing the environmental impact of heating and/or heating/cooling buildings,
reducing or preventing the risks for the environment and for human health related to the use of hazardous substances,
ensuring that proper information on the heat pump and its efficient operation is provided to the customer and the installer of the heat pump.
Assessment and verification requirements
For assessment and verification of heat pumps the applicant can group the heat pumps into basic models. The basic models shall be defined by units which are essentially the same in terms of thermal performance and function and the same or comparable in terms of basic components, specifically fans, coils, compressors and motors. The specific assessment and verification requirements are indicated immediately below each criterion. Where appropriate, test methods and standards other than those indicated for each criterion may be used if their equivalence is accepted by the competent body assessing the application. Where the applicant is required to provide declarations, documentation, analyses, test reports, or other evidence to show compliance with the criteria, it is understood that these may originate from the applicant and/or his supplier(s) and/or their supplier(s), et cetera, as appropriate. Where appropriate, competent bodies may require supporting documentation and may carry out independent verifications. The competent bodies are recommended to take into account the implementation of recognised environmental management schemes, such as EMAS or ISO 14001, when assessing applications and monitoring compliance with the criteria. (Note: it is not required to implement such management schemes). In addition, the test laboratory for noise and efficiency shall fulfil the general requirements according to the standard EN-ISO/IEC 17 025:2005. The laboratory shall be independent and accredited for testing according to relevant test methods. Other laboratories may be accepted if no laboratory accredited for testing is known of, in the country where the applicant is located. In such cases the laboratory shall be independent and competent. For information: Coefficient of performance (COP) is the ratio of heat output to electricity or gas input for a specified source and output temperature. Energy efficiency ratio (EER) is ratio of cold output to electricity or gas input for a specified source and output temperature. The primary energy ratio (PER) is given by: COP × 0,40 (or COP/2,5) for electrically driven heat pumps and by COP × 0,91 (or COP/1,1) for gas driven or gas absorption heat pumps, where 0,40 is the current European average electricity power generation efficiency including grid losses and 0,91 is the current European average gas efficiency including distribution losses according to Directive 2006/32/EC of the European Parliament and of the Council of 5 April 2006 on energy end-use efficiency and energy services and repealing Council Directive 93/76/EEC.
1. Efficiency in heating mode (COP) The efficiency of the heat pump unit shall exceed the following minimum requirements of the coefficient of performance (COP) and primary energy ratio (PER). Type of heat pump: heat source/heat sink Outdoor unit [°C] Indoor unit [°C] Min. COP Min. COP Min. PER Electric heat pump Gas heat pump air/air Inlet dry bulb: 2 Inlet wet bulb: 1 Inlet dry bulb: 20 Inlet wet bulb: 15 max 2,90 1,27 1,16 air/water Inlet dry bulb: 2 Inlet wet bulb: 1 Inlet temperature: 30 Outlet temperature: 35 3,10 1,36 1,24 Inlet temperature: 40 Outlet temperature: 45 2,60 1,14 1,04 brine/air Inlet temp.: 0 Outlet temp.: – 3 Inlet dry bulb: 20 Inlet wet bulb: 15 max 3,40 1,49 1,36 brine/water Inlet temp: 0 Outlet temp: – 3 Inlet temperature: 30 Outlet temperature: 35 4,30 1,89 1,72 Inlet temperature: 40 Outlet temperature: 45 3,50 1,54 1,40 water/water Inlet temp: 10 Outlet temp: 7 Inlet temperature: 30 Outlet temperature: 35 5,10 2,24 2,04 Inlet temperature: 40 Outlet temperature: 45 4,20 1,85 1,68 water/air Inlet temp: 15 Outlet temp: 12 Inlet dry bulb: 20 Inlet wet bulb: 15 max 4,70 2,07 1,88 (water loop source) Inlet temp: 20 Outlet temp: 17 Inlet dry bulb: 20 Inlet wet bulb: 15 max 4,40 1,93 1,76 Assessment and verification: Testing shall be performed in accordance to EN 14 511:2004. The test shall be performed at the full capacity of the heat pump in question, at the conditions specified in the table. An independent test laboratory accredited for the stated testing shall verify the given values. Heat pumps which are certified in the Eurovent certification programme or DACH certification programme or another programme approved by the competent body do not require additional testing by an independent laboratory for the given values. The test reports shall be submitted with the application.
2. Efficiency in cooling mode (EER) If the heat pump is reversible and can cool, then the efficiency of the heat pump unit shall exceed the following minimum requirements of the energy efficiency ratio (EER) in cooling mode. Type of heat pump: Outdoor unit [°C] Indoor unit [°C] Min. EER Min. EER Min. PER Electric heat pump Gas heat pump air/air Inlet dry bulb: 35 Inlet wet bulb: 24 Inlet dry bulb: 27 Inlet wet bulb: 19 3,20 1,41 1,3 air/water Inlet dry bulb: 35 Inlet wet bulb: — Inlet temperature: 23 Outlet temperature: 18 2,20 0,97 0,9 Inlet temperature: 12 Outlet temperature: 7 2,20 0,97 0,9 brine/air Inlet temp: 30 Outlet temp: 35 Inlet dry bulb: 27 Inlet wet bulb: 19 max 3,30 1,45 1,3 brine/water Inlet temp: 30 Outlet temp: 35 Inlet temperature: 23 Outlet temperature: 18 3,00 1,32 1,2 Inlet temperature: 12 Outlet temperature: 7 3,00 1,32 1,2 water/water Inlet temp: 30 Outlet temp: 35 Inlet temperature: 23 Outlet temperature: 18 3,20 1,41 1,3 Inlet temperature: 12 Outlet temperature: 7 3,20 1,41 1,3 water/air Inlet temp: 30 Outlet temp: 35 Inlet dry bulb: 27 Inlet wet bulb: 19 4,40 1,93 1,8 Assessment and verification: Testing shall be performed in accordance to EN 14 511:2004; for gas absorption heat pumps in accordance with EN12309-2:2000. The test shall be performed at the full capacity of the heat pump in question, at the conditions specified in the table. An independent test laboratory accredited for the stated testing shall verify the given values. Heat pumps which are certified in the Eurovent certification programme or DACH certification programme, or another programme approved by the competent body, do not require additional testing by an independent laboratory for the given values. The test reports shall be submitted with the application.
3. Refrigerant The global warming potential (GWP) for the refrigerant must not exceed GWP value > 2000 over a 100 year period. If the refrigerant has a GWP of less than 150 then the minimum requirements of the coefficient of performance (COP) and primary energy ratio (PER) in heating mode and the energy efficiency ratio (EER) in cooling mode, as set out in criteria 1 and 2 of this Annex, shall be reduced by 15 %. GWP values considered will be those set out in Annex 1 of Regulation (EC) No 842/2006 of the European Parliament and of the Council. Assessment and verification: The names of refrigerant/s used in the product shall be submitted with the application, along with their GWP values according to the Regulation above. The GWP values of refrigerants shall be calculated in terms of the 100-year warming potential of one kilogram of a gas relative to one kilogram of CO2. For fluorinated refrigerants, the GWP values shall be those published in the third assessment report (TAR) adopted by the Intergovernmental Panel on Climate Change (2001 IPCC GWP values for a 100 year period) For non-fluorinated gases, the GWP values are those published in the First IPCC assessment over a 100 year period. GWP values for mixtures of refrigerants shall be based on the formula stated in Annex I of the Regulation 842/2006.
4. Secondary refrigerant (Note: not applicable to all types of heat pumps within this product group) The secondary refrigerant, brine or additives must not be substances classified as environmentally hazardous or constituting a health hazard as defined by Council Directive 67/548/EEC concerning environmental hazard and its subsequent amendments. Assessment and verification: The name/s of the secondary refrigerant/s used shall be submitted with the application.
5. Noise The sound power level(s) shall be tested and stated in dB(A) on the information fiche. Assessment and verification: Testing shall be performed in accordance with ENV-12 102. The test report shall be submitted with the application.
6. Heavy metals and flame retardants Cadmium, lead, mercury, chromium 6+ or the flame retardants, i.e. poly-brominated biphenyl (PBB) or poly-brominated diphenyl ether (PBDE) flame retardants as listed in Article 4 of Directive 2002/95/EC of the European Parliament and Council, may not be used in the heat pump or in the heat pump system, taking into account the tolerances specified in Commission Decision 2005/618/EC amending Directive 2002/95/EC. This requirement for flame retardants shall take account of subsequent adaptations and amendments made to that Directive regarding the use of Deca-BDE. Assessment and verification: A certificate signed by the producer of the heat pump.
7. Installer Training The applicant shall ensure that suitable training is available for installers in Member States where the product is to be marketed. This training shall include information relevant for sizing and installing the heat pump and completing the information fiche for consumers. Assessment and verification: A declaration shall be submitted with the application describing the training available and stating where such training is available.
8. Documentation The applicant shall provide a comprehensive manual for installation, maintenance and a manual for operating the heat pump. Assessment and verification: Maintenance, installation and operation manuals shall be submitted with the heat pump and fulfil the requirements of EN378:2000 or any revision thereof.
9. Spare parts availability The applicant shall ensure the availability of spare parts for a period of 10 years from the date of sale. Assessment and verification: A declaration that spare parts will be made available for 10 years shall be submitted with the application along with an explanation of how this availability will be guaranteed.
10. Information fiche The applicant shall ensure that the blank information fiche for customers attached to this Annex is available at point of sale to provide appropriate advice to consumers about the heat pump. The completed fiche for the use of installers attached to this Annex must also be made available to installers. The applicant shall supply suitable tools, computer programs and guidance so that competent installers are able to calculate the performance parameters of the heat pump system such as seasonal performance factor, seasonal energy efficiency ratio, primary energy ratio and annual emissions of carbon dioxide. In addition the installer shall be capable of completing the information fiche for consumers prior to the consumer purchase of the equipment. Assessment and verification: The applicant must submit the completed information fiche for installers and describe how they intend to ensure that it will be made available for installers. They must also describe how they intend to ensure that the information fiche for customers is made available to them at the points of sale of their products.
11. Information appearing on the eco-label Box 2 of the Ecolabel shall include the following text: Amongst heat pumps, this product has: The following text (or equivalent text) shall appear on the packaging of the product: For more information on why this product has been awarded the Flower please visit the web-site: http://europa.eu.int/ecolabel.
higher energy efficiency,
lower global warming impact,
Guidance for purchasing an Ecolabelled heat pump — Information fiche for customers —
Warning! Read before purchasing Efficient operation of this heat pump will only be ensured if the system is correctly matched to the heating or cooling demand of the building and climate zone in which it is installed! Always consult a competent installer and ask them to complete this fiche before purchasing! The EU Ecolabel is awarded to those models of heat pump which are more energy efficient and which minimise their environmental impacts. This fiche should be completed by a qualified installer to provide you with information and recommendations about the most suitable heat pump system for your home. In this way you will obtain the benefits of the very high efficiency of heat pumps which concentrate the heat stored in the air, ground or water. Some systems are also reversible and can produce cooling through extracting heat and ejecting it to the immediate surroundings. Some systems may also provide hot water for sanitary use. Heat pumps can be selected which can be used with most distribution systems including radiators, warm air and under floor heating, and can be retrofitted to most existing heating systems with some suitable precautions as set out below.
Reducing heat loss and solar gain of buildings
If your dwelling is more than 10 years old, before choosing a heat pump, it may be cost effective to improve your insulation first, to reduce heat loss for heating you building or heat gain if you are looking to cool it. (It is actually more efficient to fit a smaller heat pump in a well insulated building, for example). If you accept the installer’s recommendations for improving insulation, the heat pump you buy should then be sized appropriately. For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult www.kyotoinhome.info
Information and recommendations for installing a heat pump in your home Customer name Address Building type: detached/semi-detached/terraced/apartment Approximate year built: 1. Description of existing heating system/building Fuel type oil/mains gas/direct electricity/coal/bottled gas/other Existing distribution system radiators/warm air/under floor heating/other Minimum design temperature for heating of current system (°C) Annual heating demand of building in current state (kW) Annual cooling demand of building in current state (kW) Maximum design temperature for cooling of current system (°C) Potential Solar heat gain of building in current state (kW) 2. Recommendations for upgrading building insulation Measures for reducing heat loss Reduced heat loss (kW): Measures for reducing solar gain Reduced solar gain (kW): 3. Recommended heat pump system Using information supplied by the manufacturer and the type and location of your dwelling, the following recommendations for your new heating or heating/cooling system are made: primary heating heat pump manufacturer model heat source ground/water/air distribution medium radiators/warm air/under floor heating/other refrigerant type and GWP value natural/artificial heat capacity (kW) heat output/electricity input seasonal efficiency over year capable of supplying domestic hot water? Yes/no auxiliary heating type heat capacity (kW) cooling (if required) cooling capacity (kW) cold output/electricity input annual energy demands and CO2 emissions annual energy consumption (kWh) equivalent carbon dioxide emissions (kg CO2): conversion factor used: Installer signature Qualifications/training Company Address Date
Guidance for installing an Ecolabelled heat pump — Information fiche for installers —
Warning! Read before purchasing Efficient operation of this heat pump requires a competent installer to design the heating system to match the heating or cooling demand of the building and climate zone and to install the system in accord with the manufacturer’s instructions The EU Ecolabel is awarded to those models of heat pump which are more energy efficient and which minimise their environmental impacts Heat pumps have a very high efficiency because they only use energy to concentrate the heat present in the ground, water or air. Some models can also operate in reverse mode and produce cooling by ejecting heat from a dwelling. The information contained in this fiche will enable you to ensure that the benefits of the heat pump unit are carried over to the collection and distribution systems and to complete the fiche which shall be given to the customer to explain your choice.
1. Minimum information to be supplied by the manufacturer manufacturer model heat collector heat distribution medium heating capacity (kW) cooling capacity (kW) hot water supply Refrigerant type noise level (dbA) parts availability from date of sale (years) coefficient of performance (heating) specifying inlet and outlet temperatures (°C) energy efficiency ratio (cooling) specifying inlet and outlet temperatures (°C) For retrofitting to existing heating systems, the heat pump should be selected to match the existing distribution system which may be ducted warm air, hot water via radiators or underfloor heating. As the outlet temperature may be lower than that of the boiler it will replace, it is essential to identify ways of reducing the heat loss or solar gain in order to maintain the same size of distribution system.
1. Definitions
Coefficient of performance (COP) is the ratio of heat output to electricity input for a specified source and output temperature. Energy efficiency ratio (EER) is the ratio of cold output to electricity input for a specified source and output temperature. Seasonal coefficient of performance (SCOP) is the coefficient of performance averaged over the length of the heating season for the heat pump system at a specified location. Seasonal energy efficiency ratio (SEER) is the energy efficiency ratio averaged over the length of the cooling season for the heat pump system at a specified location. The primary energy ratio (PER) is given by: COP × 0,40 (or COP/2,5) for heat pumps with electrically driven compressors and by COP × 0,91 (or COP/1,1) for heat pumps with gas driven compressors, where 0,40 is the current European average electricity power generation efficiency including grid losses and 0,91 is the current European average gas efficiency including distribution losses. The manufacturer shall provide programs, tools and guidelines to help you perform the following calculations. Climatic data should be appropriate for the geographical location of the building.
2. Reducing the heat loss and solar gain of buildings If the dwelling is more than 10 years old, then it will probably be cost effective to reduce the heat loss by increasing the insulation level and to reduce the solar gain by restricting the direct rays of the sun during the summer. If the customer accepts your recommendations then the system should be sized for the reduced heat loss and solar gain. For further information on reducing heat loss or solar gain or sizing and installing heat pumps systems consult www.kyotoinhome.info
3. Heat loss and sizing of the heating system The heat loss of the building shall be calculated in accordance with national practice or using a suitable validated computer program based on EN 832, the Euronorm for calculating heat loss. This heat loss should then be compared with the current values required by building codes. For existing buildings, it is generally cost effective to bring the insulation standard closer to current values before sizing the heat pump for the reduced heat loss.
3. Seasonal performance factor and energy consumption for heating
The calculation shall consider:
climate (outdoor air temperature),
design outdoor temperature,
the variation of the ground-temperature over a year (for ground-source heat pumps, both with vertical and horizontal collectors),
desired temperature indoors,
temperature level of hydronic heating systems,
annual energy demand for space heating,
annual energy demand for domestic hot water (if applicable),
Primary Energy Ratio (PER) and Annual CO2 emissions
The average efficiency for power/gas generation as well as electric grid/gas distribution losses to be used in the calculation. CO2 emissions and savings to be calculated based on the primary energy usage.
4. Solar gain and sizing of the cooling system If the system can also produce cooling then the solar gain of the building shall be calculated in accordance with national practice or using a validated computer program. This gain should then be compared with the current values required by building codes. For existing buildings, it is generally cost effective to reduce the solar gain before sizing the heat pump for the reduced solar gain.
4. Seasonal energy efficiency ratio and energy consumption for cooling
The calculation shall consider:
climate (outdoor air temperature),
design outdoor temperature,
the variation of the ground-temperature over a year (for ground-source heat pumps, both with vertical and horizontal collectors),
desired temperature indoors,
temperature level of hydronic heating systems,
annual energy demand for space cooling.
Primary Energy Ratio (PER) and Annual CO2 emissions
The average efficiency for power/gas generation as well as electric grid/gas distribution losses to be used in the calculation. CO2 emissions and savings to be calculated based on the primary energy usage.
5. Training for installers and drillers Suitable courses are available in most Member States to enable installers to obtain appropriate national or European accredited qualifications. Manufacturers shall either organise their own courses to assist installers with using their equipment or work with local training institutes to provide such information as part of their courses. For ground source heat pumps where a vertical bore hole is required, suitable courses for drillers are available in some Member States.
Versions
Cited by
- Commission Decision of 15 March 2013 amending Decisions 2007/506/EC and 2007/742/EC in order to prolong the validity of the ecological criteria for the award of the EU Ecolabel to certain products (notified under document C(2013) 1411) (Text with EEA relevance) (2013/135/EU) Decision · Grade B
Commission Decision 2007/742/EC of 9 November 2007 establishing the ecological criteria for the award of the Community eco-label to electrically driven, gas driven or gas absorption heat pumps expires on 31 March 2013.
- Commission Decision of 30 November 2009 amending Decisions 2002/741/EC, 2002/747/EC, 2003/200/EC, 2005/341/EC, 2005/342/EC, 2005/343/EC, 2005/344/EC, 2005/360/EC, 2006/799/EC, 2007/64/EC, 2007/506/EC and 2007/742/EC in order to prolong the validity of the ecological criteria for the award of the Community Ecolabel to certain products (notified under document C(2009) 9599) (Text with EEA relevance) (2009/888/EC) Decision · Grade B
Commission Decision 2007/742/EC of 9 November 2007 establishing the ecological criteria for the award of the Community eco-label to electrically driven, gas driven or gas absorption heat pumps expires on 9 November 2010.
- Commission Decision of 14 November 2011 amending Decisions 2006/799/EC, 2007/64/EC, 2007/506/EC, 2007/742/EC, 2009/543/EC and 2009/544/EC in order to prolong the validity of the ecological criteria for the award of the EU Ecolabel to certain products (notified under document C(2011) 8041) (Text with EEA relevance) (2011/740/EU) Decision · Grade B
Commission Decision 2007/742/EC of 9 November 2007 establishing the ecological criteria for the award of the Community eco-label to electrically driven, gas driven or gas absorption heat pumps expires on 31 December 2011.
- Commission Decision of 14 November 2011 amending Decisions 2006/799/EC, 2007/64/EC, 2007/506/EC, 2007/742/EC, 2009/543/EC and 2009/544/EC in order to prolong the validity of the ecological criteria for the award of the EU Ecolabel to certain products (notified under document C(2011) 8041) (Text with EEA relevance) (2011/740/EU) Decision · Grade B
Given the different stages of the revision process for those Decisions, it is appropriate to prolong the periods of validity of the ecological criteria and the related assessment and verification requirements which they set out. The period of validity of the ecological criteria and the related assessment and verification requirements set out in Decisions 2006/799/EC and 2007/64/EC should be prolonged until 31 December 2013. The period of validity of the ecological criteria and the related assessment and verification requirements set out in Decision 2007/506/EC should be prolonged until 31 Marc
- Commission Decision of 28 May 2014 establishing the criteria for the award of the EU Ecolabel for water-based heaters (notified under document C(2014) 3452) (Text with EEA relevance) (2014/314/EU) Decision · Grade B
Applications for the EU Ecolabel for heat pumps which provide heat to a water based central heating system falling within the product group electrically driven, gas driven or gas absorption heat pumps submitted within two months from the date of adoption of this Decision may be based either on the criteria set out in Commission Decision 2007/742/EC, or on the criteria set out in this Decision. Applications shall be evaluated in accordance with the criteria on which they are based.
- Commission Decision of 28 May 2014 establishing the criteria for the award of the EU Ecolabel for water-based heaters (notified under document C(2014) 3452) (Text with EEA relevance) (2014/314/EU) Decision · Grade B
EU Ecolabel licences awarded to heat pumps which provide heat to water based central heating system in accordance with the criteria set out in Decision 2007/742/EC may be used for 12 months from the date of adoption of this Decision.
- Directive 2009/28/EC of the European Parliament and of the Council of 23 April 2009 on the promotion of the use of energy from renewable sources and amending and subsequently repealing Directives 2001/77/EC and 2003/30/EC (Text with EEA relevance) Act · Grade B
With respect to their building regulations and codes, Member States shall promote the use of renewable energy heating and cooling systems and equipment that achieve a significant reduction of energy consumption. Member States shall use energy or eco-labels or other appropriate certificates or standards developed at national or Community level, where these exist, as the basis for encouraging such systems and equipment. In the case of biomass, Member States shall promote conversion technologies that achieve a conversion efficiency of at least 85 % for residential and commercial applications and
- Commission Decision of 13 June 2014 amending Decision 2007/742/EC on electrically driven, gas driven or gas absorption heat pumps (notified under document C(2014) 3838) (Text with EEA relevance) (2014/363/EU) Decision · Grade B
Commission Decision 2007/742/EC of 9 November 2007 establishing the ecological criteria for the award of the Community eco-label to electrically driven, gas driven or gas absorption heat pumps expires on 31 October 2014.
- Commission Decision of 13 June 2014 amending Decision 2007/742/EC on electrically driven, gas driven or gas absorption heat pumps (notified under document C(2014) 3838) (Text with EEA relevance) (2014/363/EU) Decision · Grade B
An assessment has been carried out to evaluate the relevance and appropriateness of the current ecological criteria, as well as of the related assessment and verification requirements, established by this Decision. Given the different stages of the revision process for this Decision, it is appropriate to prolong the period of validity of the ecological criteria and the related assessment and verification requirements which it sets out. The period of validity of the ecological criteria and the related assessment and verification requirements set out in Decision 2007/742/EC should be prolonged u
- Commission Decision of 13 June 2014 amending Decision 2007/742/EC on electrically driven, gas driven or gas absorption heat pumps (notified under document C(2014) 3838) (Text with EEA relevance) (2014/363/EU) Decision · Grade B
Decision 2007/742/EC should therefore be amended accordingly,
- Commission Decision of 13 June 2014 amending Decision 2007/742/EC on electrically driven, gas driven or gas absorption heat pumps (notified under document C(2014) 3838) (Text with EEA relevance) (2014/363/EU) Decision · Grade B
Decision 2007/742/EC is amended as follows:
- Commission Decision of 30 October 2013 amending Decision 2007/742/EC in order to prolong the validity of the ecological criteria for the award of the EU Ecolabel to electrically driven, gas driven or gas absorption heat pumps (notified under document C(2013) 7154) (Text with EEA relevance) (2013/633/EU) Decision · Grade B
Commission Decision 2007/742/EC expires on 31 December 2013.
- Commission Decision of 30 October 2013 amending Decision 2007/742/EC in order to prolong the validity of the ecological criteria for the award of the EU Ecolabel to electrically driven, gas driven or gas absorption heat pumps (notified under document C(2013) 7154) (Text with EEA relevance) (2013/633/EU) Decision · Grade B
An assessment has been carried out to evaluate the relevance and appropriateness of the current ecological criteria, as well as of the related assessment and verification requirements, established by this Decision. Given the stage of the revision process for this Decision, it is appropriate to prolong the period of validity of the ecological criteria and the related assessment and verification requirements which it sets out. The period of validity of the ecological criteria and the related assessment and verification requirements set out in Decision 2007/742/EC should be prolonged until 31 Oct
- Commission Decision of 30 October 2013 amending Decision 2007/742/EC in order to prolong the validity of the ecological criteria for the award of the EU Ecolabel to electrically driven, gas driven or gas absorption heat pumps (notified under document C(2013) 7154) (Text with EEA relevance) (2013/633/EU) Decision · Grade B
Decision 2007/742/EC should therefore be amended accordingly.
- Commission Decision (EU) 2017/175 of 25 January 2017 on establishing EU Ecolabel criteria for tourist accommodation (notified under document C(2017) 299) (Text with EEA relevance) Decision · Grade B
The applicant shall provide technical specifications from the manufacturer or the professional technicians responsible for installation, sale or maintenance of the air-based heat pump indicating how the required efficiency is met (if applicable). Where EU Ecolabel heat pump products are used, the applicant shall provide a copy of the EU Ecolabel certificate or a copy of the label on the package showing that it was awarded in accordance with Decision 2007/742/EC. Where products bearing other ISO type I labels are used, the applicant shall provide a copy of the type I label certificate or a copy
- Commission Decision (EU) 2017/175 of 25 January 2017 on establishing EU Ecolabel criteria for tourist accommodation (notified under document C(2017) 299) (Text with EEA relevance) Decision · Grade B
Air-based heat pumps up to 100 kW heat output (3 points) The tourist accommodation shall have at least an air-based heat pump meeting criterion 7 (if applicable, see note in criterion 7 and awarded the EU Ecolabel in accordance with Commission Decision 2007/742/EC or other ISO Type I label.