Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers
Grade B
mapped from publisher markup. A grade says how a document's structure was obtained, not how reliable the law is.
Address https://gelex.eu/eli/EU/regulation/2014/548@2014-05-21/en
Contents
- Preamble
- ANNEX
- ANNEX I Ecodesign requirements
- 1.
- 1.1. Table I.1: Maximum load and no-load losses (in W) for three-phase liquid-immersed medium power transformers with one winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV Table I.2: Maximum load and no-load losses (in W) for three –phase dry-type medium power transformers with one winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV. Table I.3: Correction of load and no load losses in case of other combinations of winding voltages or dual voltage in one or both windings (rated power ≤ 3150 kVA)
- 1.2. Table I.4: Minimum Peak Efficiency Index (PEI) values for liquid immersed medium power transformers Table I.5: Minimum Peak Efficiency Index (PEI) values for dry type medium power transformers
- 1.4. Table I.6: Maximum load and no-load losses (in W) for medium power liquid immersed pole-mounted transformers
- 2. Table I.7: Minimum Peak Efficiency Index requirements for liquid immersed large power transformers Table I.8: Minimum Peak Efficiency Index requirements for dry-type large power transformers
- 3.
- 4.
- ANNEX II Measurement and calculation methods
- Measurement method
- Calculation methods
- ANNEX III Table Verification procedure
- ANNEX IV Indicative Benchmarks
THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Having regard to Directive 2009/125/EC of the European Parliament and of the Council of 21 October 2009 establishing a framework for the setting of ecodesign requirements for energy-related products, and in particular Article 15(1) thereof,
After consulting the Ecodesign Consultation Forum,
Whereas:
(1) The Commission has carried out a preparatory study that analysed the environmental and economic aspects of transformers. The study was developed together with stakeholders and interested parties from the Union and the results have been have made publicly available. Transformers are considered as energy related products within the meaning of Article 2(1) of Directive 2009/125/EC.
(2) The study showed that energy in the use phase is the most significant environmental aspect that can be addressed through product design. Significant amounts of raw materials (copper, iron, resin, aluminium) are used in the manufacturing of transformers, but market mechanisms seem to be ensuring an adequate end-of-life treatment, and therefore it is not necessary to establish related ecodesign requirements.
(3) Ecodesign requirements set out in Annex I apply to products placed on the market or put into service wherever they are installed. Therefore such requirements cannot be made dependant on the application in which the product is used.
(4) Transformers are usually purchased under framework agreements. In this context, purchase refers to the act of contracting with the manufacturer for the delivery of a given volume of transformers. The contract is deemed to have come into force on the date of signature by the parties.
(5) Certain categories of transformers should not be covered by this Regulation, due to their specific function,. The energy consumption and saving potential of such transformers is negligible compared to other transformers.
(6) Regulatory concessions are granted because of the weight limitations for mounting transformers on utility poles. In order to avoid misuse of transformers specifically manufactured for pole-mounted operation, they should include a visible display For pole-mounted operation only, so as to facilitate the work of national market surveillance authorities.
(7) Regulatory concessions are granted to transformers equipped with equipment capable of performing voltage regulation functions to integrate distributed generation from renewable sources into the distribution grid. Such concessions should gradually be phased out as this emerging technology matures and measurement standards become available to separate the losses associated to the core transformer from those associated to the equipment performing additional functions.
(8) Ecodesign requirements for the energy performance/efficiency of medium power transformers and for the energy efficiency of large power transformers should be set with a view to harmonising ecodesign requirements for these devices throughout the Union. Such requirements would also contribute to the efficient functioning of the internal market and to improving Member States' environmental performance.
(9) Establishment of ecodesign requirements for medium and large power transformers is also necessary to increase the market penetration of technologies and design options improving their energy performance or efficiency. Total losses of the transformers fleet in the EU27 in 2008 amounted to 93,4 TWh per year. The cost-effective improvement potential through more efficient design has been estimated in about 16,2 TWh per year in 2025, which corresponds to 3,7 Mt of CO2 emissions.
(10) It is necessary to provide for a staged entry into force of the ecodesign requirements in order to provide an appropriate timeframe for manufacturers to redesign their products. Time limits for the implementation of those requirements should be set taking into account impacts on the costs for manufacturers, in particular small and medium size enterprises, while ensuring timely achievement of the policy objectives.
(11) To allow an effective implementation of the regulation, National Regulating Authorities are strongly advised to take account of the effect of minimum efficiency requirements on the initial cost of the transformer and to allow for the installation of more efficient transformers than the regulation requires, whenever these are economically justified on a whole life cycle basis, including an adequate evaluation of losses reduction.
(12) To facilitate compliance checks, manufacturers should be asked to provide information in the technical documentation referred to in Annexes IV and V to Directive 2009/125/EC.
(13) The measures provided for in this Regulation are in accordance with the opinion of the Committee established by Article 19(1) of Directive 2009/125/EC,
HAS ADOPTED THIS REGULATION:
Article 1 Subject matter and scope
1. This Regulation establishes ecodesign requirements for placing on the market or putting into service power transformers with a minimum power rating of 1 kVA used in 50 Hz electricity transmission and distribution networks or for industrial applications. The Regulation is only applicable to transformers purchased after the entry into force of the Regulation.
2. This Regulation shall not apply to transformers specifically designed and used for the following applications: except as regards the product information requirements and technical documentation set out in Annex I, points 3 and 4.
instrument transformers, specifically designed to supply measuring instruments, meters, relays and other similar apparatus,
transformers with low-voltage windings specifically designed for use with rectifiers to provide a DC supply,
transformers specifically designed to be directly connected to a furnace,
transformers specifically designed for offshore applications and floating offshore applications,
transformers specially designed for emergency installations,
transformers and auto-transformers specifically designed for railway feeding systems,
earthing or grounding transformers, this is, three-phase transformers intended to provide a neutral point for system grounding purposes,
traction transformers mounted on rolling stock, this is, transformers connected to an AC or DC contact line, directly or through a converter, used in fixed installations of railway applications,
starting transformers, specifically designed for starting three-phase induction motors so as to eliminate supply voltage dips,
testing transformers, specifically designed to be used in a circuit to produce a specific voltage or current for the purpose of testing electrical equipment,
welding transformers, specifically designed for use in arc welding equipment or resistance welding equipment,
transformers specifically designed for explosion-proof and underground mining applications,
transformers specifically designed for deep water (submerged) applications,
medium Voltage (MV) to Medium Voltage (MV) interface transformers up to 5 MVA,
large power transformers where it is demonstrated that for a particular application, technically feasible alternatives are not available to meet the minimum efficiency requirements set out by this Regulation,
large power transformers which are like for like replacements in the same physical location/installation for existing large power transformers, where this replacement cannot be achieved without entailing disproportionate costs associated to their transportation and/or installation,
Article 2 Definitions
For the purpose of this Regulation and its annexes the following definitions shall apply.
(1) Power transformer means a static piece of apparatus with two or more windings which, by electromagnetic induction, transforms a system of alternating voltage and current into another system of alternating voltage and current usually of different values and at the same frequency for the purpose of transmitting electrical power.
(2) Small power transformer means a power transformer with a highest voltage for equipment not exceeding 1,1 kV.
(3) Medium power transformer means a power transformer with a highest voltage for equipment higher than 1,1 kV, but not exceeding 36 kV and a rated power equal to or higher than 5 kVA but lower than 40 MVA.
(4) Large power transformer means a power transformer with a highest voltage for equipment exceeding 36 kV and a rated power equal or higher than 5 kVA, or a rated power equal to or higher than 40 MVA regardless of the highest voltage for equipment.
(5) Liquid-immersed transformer means a power transformer in which the magnetic circuit and windings are immersed in liquid.
(6) Dry-type transformer means a power transformer in which the magnetic circuit and windings are not immersed in an insulating liquid.
(7) Medium power pole mounted transformer means a power transformer with a rated power of up to 315 kVA suitable for outdoor service and designed to be mounted on the support structures of overhead power lines.
(8) Voltage Regulation Distribution Transformer means a medium power transformer equipped with additional components, inside or outside of the transformer tank, to automatically control the input or output voltage of the transformer for on-load voltage regulation purposes.
(9) Winding refers to the assembly of turns forming an electrical circuit associated with one of the voltages assigned to the transformer.
(10) Rated voltage of a winding (Ur) is the voltage assigned to be applied, or developed at no-load, between the terminals of an untapped winding, or of a tapped winding connected on the principal tapping.
(11) High-voltage winding refers to the winding having the highest rated voltage.
(12) Highest voltage for equipment (Um) applicable to a transformer winding is the highest r.m.s phase-to-phase voltage in a three-phase system for which a transformer winding is designed in respect of its insulation.
(13) Rated power (Sr) is a conventional value of apparent power assigned to a winding which, together with the rated voltage of the winding, determines its rated current.
(14) Load loss (Pk) means the absorbed active power at rated frequency and reference temperature associated with a pair of windings when the rated current (tapping current) is flowing through the line terminal(s) of one of the windings and the terminals of the other windings are in short-circuit with any winding fitted with tappings connected to its principal tapping, while further windings, if existing, are open-circuited.
(15) No load loss (Po) means the active power absorbed at rated frequency when the transformer is energised and the secondary circuit is open. The applied voltage is the rated voltage, and if the energized winding is fitted with a tapping, it is connected to its principal tapping.
(16) Peak Efficiency Index (PEI) means the maximum value of the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer.
Article 3 Eco-design requirements
Small power transformers, medium power transformers and large power transformer shall meet the ecodesign requirements set out in Annex I.
Article 4 Conformity Assessment
Conformity assessment shall be carried out applying the internal design control procedure set out in Annex IV to Directive 2009/125/EC or the management system procedure set out in Annex V to that Directive.
Article 5 Verification procedure for market surveillance purposes
When performing the market surveillance checks referred to in Directive 2009/125/EC, Article 3(2), Member State authorities shall apply the verification procedure set out in Annex III to this Regulation.
Article 6 Indicative Benchmarks
The indicative benchmarks for the best-performing transformers technologically possible at the time of adoption of this Regulation are identified in Annex IV.
Article 7 Review
No later than three years after the entry into force, the Commission shall review this Regulation in the light of technological progress and present the results of this review to the Consultation Forum. Specifically, the review will assess, at least, the following issues:
the possibility to set out minimum values of the Peak Efficiency Index for all medium power transformers, including those with a rated power below 3150 kVA,
the possibility to separate the losses associated to the core transformer from those associated with other components performing voltage regulation functions, where this is the case,
the appropriateness of establishing minimum performance requirements for single-phase power transformers, as well as for small power transformers,
whether concessions made for pole-mounted transformers and for special combinations of winding voltages for medium power transformers are still appropriate,
the possibility of covering environmental impacts other than energy in the use phase.
Article 8 Entry into force
The Regulation shall enter into force on the 20th day following its publication in the Official Journal of the European Union.
This Regulation shall be binding in its entirety and directly applicable in all Member States. Done at Brussels, 21 May 2014. For the Commission The President José Manuel Barroso
ANNEX
ANNEX I Ecodesign requirements
1. Minimum energy performance or efficiency requirements for medium power transformers Medium power transformers shall comply with the maximum allowed load and no-load losses or the Peak Efficiency Index (PEI) values set out in Tables I.1 to I.5, excluding medium power pole-mounted transformers, which shall comply with the maximum allowed load and no load losses values set out in Table I.6.
1.
1.1. Table I.1: Maximum load and no-load losses (in W) for three-phase liquid-immersed medium power transformers with one winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV Table I.2: Maximum load and no-load losses (in W) for three –phase dry-type medium power transformers with one winding with Um ≤ 24 kV and the other one with Um ≤ 1,1 kV. Table I.3: Correction of load and no load losses in case of other combinations of winding voltages or dual voltage in one or both windings (rated power ≤ 3150 kVA)
Requirements for three-phase medium power transformers with rated power ≤ 3150 kVA Tier 1 (from 1 July 2015) Tier 2 (from 1 July 2021) Rated Power (kVA) Maximum load losses Pk (W) Maximum no-load losses Po (W) Maximum load losses Pk (W) Maximum no-load losses Po (W) ≤ 25 Ck (900) Ao (70) Ak (600) Ao – 10 % (63) 50 Ck (1100) Ao (90) Ak (750) Ao – 10 % (81) 100 Ck (1750) Ao (145) Ak (1250) Ao – 10 % (130) 160 Ck (2350) Ao (210) Ak (1750) Ao – 10 % (189) 250 Ck (3250) Ao (300) Ak (2350) Ao – 10 % (270) 315 Ck (3900) Ao (360) Ak (2800) Ao – 10 % (324) 400 Ck (4600) Ao (430) Ak (3250) Ao – 10 % (387) 500 Ck (5500) Ao (510) Ak (3900) Ao – 10 % (459) 630 Ck (6500) Ao (600) Ak (4600) Ao – 10 % (540) 800 Ck (8400) Ao (650) Ak (6000) Ao – 10 % (585) 1000 Ck (10500) Ao (770) Ak (7600) Ao – 10 % (693) 1250 Bk (11000) Ao (950) Ak (9500) Ao – 10 % (855) 1600 Bk (14000) Ao (1200) Ak (12000) Ao – 10 % (1080) 2000 Bk (18000) Ao (1450) Ak (15000) Ao – 10 % (1305) 2500 Bk (22000) Ao (1750) Ak (18500) Ao – 10 % (1575) 3150 Bk (27500) Ao (2200) Ak (23000) Ao – 10 % (1980) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Rated Power (kVA) Maximum load losses Pk (W) Maximum no-load losses Po (W) Maximum load losses Pk (W) Maximum no-load losses Po (W) ≤ 50 Bk (1700) Ao (200) Ak (1500) Ao – 10 % (180) 100 Bk (2050) Ao (280) Ak (1800) Ao – 10 % (252) 160 Bk (2900) Ao (400) Ak (2600) Ao – 10 % (360) 250 Bk (3800) Ao (520) Ak (3400) Ao – 10 % (468) 400 Bk (5500) Ao (750) Ak (4500) Ao – 10 % (675) 630 Bk (7600) Ao (1100) Ak (7100) Ao – 10 % (990) 800 Ak (8000) Ao (1300) Ak (8000) Ao – 10 % (1170) 1000 Ak (9000) Ao (1550) Ak (9000) Ao – 10 % (1395) 1250 Ak (11000) Ao (1800) Ak (11000) Ao – 10 % (1620) 1600 Ak (13000) Ao (2200) Ak (13000) Ao – 10 % (1980) 2000 Ak (16000) Ao (2600) Ak (16000) Ao – 10 % (2340) 2500 Ak (19000) Ao (3100) Ak (19000) Ao – 10 % (2790) 3150 Ak (22000) Ao (3800) Ak (22000) Ao – 10 % (3420) One winding with Um ≤ 24 kV and the other with Um > 1,1 kV The maximum allowable losses in Tables I.1 and I.2 shall be increased by 10 % for no load losses and by 10 % for load losses One winding with Um = 36 kV and the other with Um ≤ 1,1 kV The maximum allowable losses in Tables I.1 and I.2 shall be increased by 15 % for no load losses and by 10 % for load losses One winding with Um = 36 kV and the other with Um > 1,1 kV The maximum allowable losses indicated in Tables I.1 and I.2 shall be increased by 20 % for no load losses and by 15 % for load losses Case of dual voltage on one winding In case of transformers with one high-voltage winding and two voltages available from a tapped low-voltage winding, losses shall be calculated based on the higher voltage of the low-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and 1.2. The maximum available power on the lower voltage of the low-voltage winding on such transformers shall be limited to 0,85 of the rated power assigned to the low-voltage winding at its higher voltage. In case of transformers with one low-voltage winding with two voltages available from a tapped high-voltage winding, losses shall be calculated based on the higher voltage of the high-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and I.2., The maximum available power on the lower voltage of the high-voltage winding on such transformer shall be limited to 0,85 of the rated power assigned to the high-voltage winding at its higher voltage. If the full nominal power is available regardless of the combination of voltages, the levels of losses indicated in Tables I.1 and I.2 can be increased by 15 % for no load losses and by 10 % for load losses. Case of dual voltage on both windings The maximum allowable losses in Tables I.1 and I.2 can be increased by 20 % for no load losses and by 20 % for load losses for transformers with dual voltage on both windings. The level of losses is given for the highest possible rated power and on the basis that the rated power is the same regardless of the combination of voltages.
1.2. Table I.4: Minimum Peak Efficiency Index (PEI) values for liquid immersed medium power transformers Table I.5: Minimum Peak Efficiency Index (PEI) values for dry type medium power transformers
Requirements for medium power transformers with rated power > 3150 kVA Rated Power (kVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) 3150 < Sr ≤ 4000 99,465 99,532 5000 99,483 99,548 6300 99,510 99,571 8000 99,535 99,593 10000 99,560 99,615 12500 99,588 99,640 16000 99,615 99,663 20000 99,639 99,684 25000 99,657 99,700 31500 99,671 99,712 40000 99,684 99,724 Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.4 shall be calculated by linear interpolation. Rated Power (kVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) 3150 < Sr ≤ 4000 99,348 99,382 5000 99,354 99,387 6300 99,356 99,389 8000 99,357 99,390 ≥ 10000 99,357 99,390 Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.5 shall be calculated by linear interpolation.
1.3. Requirements for medium power transformers with rated power ≤ 3150 kVA equipped with tapping connections suitable for operation while being energised or on-load for voltage adaptation purposes. Voltage Regulation Distribution Transformers are included in this category. The maximum allowable levels of losses set out in Tables I.1 and I.2 shall be increased by 20 % for no load losses and 5 % for load losses in Tier 1 and by 10 % for no load losses in Tier 2.
1.4. Table I.6: Maximum load and no-load losses (in W) for medium power liquid immersed pole-mounted transformers
Requirements for medium power pole-mounted transformers The levels of load and no load losses indicated in Tables I.1 and I.2 are not applicable to liquid immersed pole-mounted transformers with power ratings between 25 kVA and 315 kVA. For these specific models of medium power pole-mounted transformers, the maximum levels of allowable losses are set out in Table I.6. Tier 1 (1 July 2015) Tier 2 (1 July 2021) Rated Power (kVA) Maximum load losses (in W) Maximum no-load losses (in W) Maximum load losses (in W) Maximum no-load losses (in W) 25 Ck (900) Ao (70) Bk (725) Ao (70) 50 Ck (1100) Ao (90) Bk (875) Ao (90) 100 Ck (1750) Ao (145) Bk (1475) Ao (145) 160 Ck + 32 % (3102) Co (300) Ck + 32 % (3102) Co – 10 % (270) 200 Ck (2750) Co (356) Bk (2333) Bo (310) 250 Ck (3250) Co (425) Bk (2750) Bo (360) 315 Ck (3900) Co (520) Bk (3250) Bo (440)
2. Table I.7: Minimum Peak Efficiency Index requirements for liquid immersed large power transformers Table I.8: Minimum Peak Efficiency Index requirements for dry-type large power transformers
Minimum energy efficiency requirements for large power transformers The minimum efficiency requirements for large power transformers are set out in Tables I.7 and I.8. Rated Power (MVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) ≤ 4 99,465 99,532 5 99,483 99,548 6,3 99,510 99,571 8 99,535 99,593 10 99,560 99,615 12,5 99,588 99,640 16 99,615 99,663 20 99,639 99,684 25 99,657 99,700 31,5 99,671 99,712 40 99,684 99,724 50 99,696 99,734 63 99,709 99,745 80 99,723 99,758 ≥ 100 99,737 99,770 Minimum PEI values for MVA ratings that fall in between the ratings given in Table I.7 shall be calculated by linear interpolation. Rated Power (MVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) ≤ 4 99,158 99,225 5 99,200 99,265 6,3 99,242 99,303 8 99,298 99,356 10 99,330 99,385 12,5 99,370 99,422 16 99,416 99,464 20 99,468 99,513 25 99,521 99,564 31,5 99,551 99,592 40 99,567 99,607 50 99,585 99,623 ≥ 63 99,590 99,626 Minimum PEI values for MVA ratings that fall in between the ratings given in Table I.8 shall be calculated by linear interpolation.
3. Product information requirements From 1 July 2015, the following product information requirements for transformers included in the scope of this Regulation (Article 1) shall be included in any related product documentation, including free access websites of manufacturers: The information under a); c) and d) shall also be included on the rating plate of the power transformers.
3.
(a) information on rated power, load loss and no-load loss and the electrical power of any cooling system required at no load;
(b) for medium power (where applicable) and large power transformers, the value of the Peak Efficiency Index and the power at which it occurs;
(c) for dual voltage transformers, the maximum rated power at the lower voltage, according to Table I.3;
(d) information on the weight of all the main components of a power transformer (including at least the conductor, the nature of the conductor and the core material);
(e) For medium power pole mounted transformers, a visible display For pole-mounted operation only.
4. Technical documentation The following information shall be included in the technical documentation of power transformers: If (parts of) the technical documentation is based upon (parts of) the technical documentation of another model, the model identifier of that model shall be provided and the technical documentation shall provide the details of how the information is derived from the technical documentation of the other model, e.g. on calculations or extrapolations, including the tests undertaken by the manufacturer to verify the calculations or extrapolations undertaken.
4.
(a) manufacturer's name and address;
(b) model identifier, the alphanumeric code to distinguish one model from other models of the same manufacturer;
(c) the information required under point 3.
ANNEX II Measurement and calculation methods
Measurement method
For the purpose of compliance with the requirements of this Regulation, measurements shall be made using a reliable, accurate and reproducible measurement procedure, which takes into account the generally recognised state of the art measurement methods, including methods set out in documents the reference numbers of which have been published for that purpose in the Official Journal of the European Union.
Calculation methods
The methodology for calculating the Peak Efficiency Index (PEI) for medium and large power transformers is based on the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer. PEI12P0Pc0SrP0Pc0Pk Where:
P0 is the no load losses measure at rated voltage and rated frequency, on the rated tap
Pc0 is the electrical power required by the cooling system for no load operation
Pk is the measured load loss at rated current and rated frequency on the rated tap corrected to the reference temperature
Sr is the rated power of the transformer or autotransformer on which Pk is based
ANNEX III Table Verification procedure
When performing the market surveillance checks referred to in Article 3(2) of Directive 2009/125/EC, the authorities of the Member States shall apply the following verification procedure for the requirements set out in Annex I. Member States authorities shall use the measurement methods and calculation methods set out in Annex II. Given the weight and size limitations in the transportation of medium and large power transformers, Member States authorities may decide to undertake the verification procedure at the premises of manufacturers, before they are put into service in their final destination. The verification tolerances set out in this Annex relate only to the verification of the measured parameters by Member States authorities and shall not be used by the manufacturer or importer as an allowed tolerance to establish the values in the technical documentation. Measured parameter Verification tolerances Load losses The measured value shall not be greater than the declared value by more than 5 %. No load losses The measured value shall not be greater than the declared value by more than 5 %. The electrical power required by the cooling system for no load operation The measured value shall not be greater than the declared value by more than 5 %.
Verification procedure
(1) Member States authorities shall test one single unit per model;
(2) The model shall be considered to comply with the applicable requirements set out in Annex I of this Regulation if the values in the technical documentation comply with the requirements set out in Annex I, and if the measured parameters meet the requirements set out in Annex I within the verification tolerances indicated in the Table of this Annex;
(3) If the results referred to in point 2 are not achieved, the model shall be considered not to comply with this Regulation. The Member States authorities shall provide all relevant information, including the test results if applicable, to the authorities of the other Member States and the Commission within one month of the decision being taken on the non-compliance of the model.
ANNEX IV Indicative Benchmarks
At the time of adoption of this Regulation, the best available technology on the market for medium power transformers was identified as follows: The availability of material to manufacture transformers with amorphous steel core needs further development, before such values of losses can be considered to become minimum requirements in the future.
(a) Liquid-immersed medium power transformers: Ao – 20 %, Ak – 20 %
(b) Dry-type medium power transformers: Ao – 20 %, Ak – 20 %
(c) Medium power transformers with amorphous steel core: Ao – 50 %, Ak – 50 %
Versions
Cited by
- Commission Delegated Regulation (EU) 2021/2139 of 4 June 2021 supplementing Regulation (EU) 2020/852 of the European Parliament and of the Council by establishing the technical screening criteria for determining the conditions under which an economic activity qualifies as contributing substantially to climate change mitigation or climate change adaptation and for determining whether that economic activity causes no significant harm to any of the other environmental objectives (Text with EEA relevance) Regulation · Grade B
installation of transmission and distribution transformers that comply with the Tier 2 (1 July 2021) requirements set out in Annex I to the Commission Regulation (EU) No 548/2014 and, for medium power transformers with highest voltage for equipment not exceeding 36 kV, with AAA0 level requirements on no-load losses set out in standard EN 50588-1.
- Commission Regulation (EU) 2016/2282 of 30 November 2016 amending Regulations (EC) No 1275/2008, (EC) No 107/2009, (EC) No 278/2009, (EC) No 640/2009, (EC) No 641/2009, (EC) No 642/2009, (EC) No 643/2009, (EU) No 1015/2010, (EU) No 1016/2010, (EU) No 327/2011, (EU) No 206/2012, (EU) No 547/2012, (EU) No 932/2012, (EU) No 617/2013, (EU) No 666/2013, (EU) No 813/2013, (EU) No 814/2013, (EU) No 66/2014, (EU) No 548/2014, (EU) No 1253/2014, (EU) 2015/1095, (EU) 2015/1185, (EU) 2015/1188, (EU) 2015/1189 and (EU) 2016/2281 with regard to the use of tolerances in verification procedures (Text with EEA relevance) Regulation · Grade B
Annex III to Regulation (EU) No 548/2014 is amended in accordance with Annex XIX to this Regulation.
- Commission Implementing Regulation (EU) 2015/763 of 12 May 2015 imposing a provisional anti-dumping duty on imports of certain grain-oriented flat-rolled products of silicon-electrical steel originating in the People's Republic of China, Japan, the Republic of Korea, the Russian Federation and the United States of America Regulation · Grade B
As regards the quality of the product concerned, the product of one Japanese producer is considered as the benchmark in quality terms within the GOES and transformers industry. However, two Union producers are generally recognised to be able to produce certain quality types with low core losses of the product concerned. In addition, other Union producers are catching up now, and have decided to start producing proportionally more high permeability than conventional types of the product concerned, also as a result of the first phase of the implementation of Commission Regulation (EU) No 548/201
- Commission Implementing Regulation (EU) 2015/763 of 12 May 2015 imposing a provisional anti-dumping duty on imports of certain grain-oriented flat-rolled products of silicon-electrical steel originating in the People's Republic of China, Japan, the Republic of Korea, the Russian Federation and the United States of America Regulation · Grade B
If no anti-dumping duties were imposed, it would become uncertain whether the Union industry would be able to further develop its high permeability types of GOES which are necessary for the implementation of Tier 1 of Regulation (EU) No 548/2014, taking into consideration the accumulated losses incurred since 2011.
- Council Decision (EU) 2019/466 of 18 March 2019 on the position to be taken on behalf of the European Union within the Association Council established by the Association Agreement between the European Union and the European Atomic Energy Community and their Member States, of the one part, and Ukraine, of the other part, as regards the amendment of Annex XXVII to that Agreement Decision · Grade B
Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers Timetable: the timetable for the implementation of the Regulation's provisions shall be determined by 31 December 2021.
- Commission Delegated Regulation (EU) 2023/2485 of 27 June 2023 amending Delegated Regulation (EU) 2021/2139 establishing additional technical screening criteria for determining the conditions under which certain economic activities qualify as contributing substantially to climate change mitigation or climate change adaptation and for determining whether those activities cause no significant harm to any of the other environmental objectives (Text with EEA relevance) Regulation · Grade B
transmission and distribution current-carrying wiring devices and non-current-carrying wiring devices for wiring electrical circuits, and transformers that comply with the Tier 2 (1 July 2021) requirements for large power transformers set out in Annex I to Commission Regulation (EU) No 548/2014*8, and medium power transformers with highest voltage for equipment not exceeding 36 kV, with AA0 level requirements on no-load losses set out in standard EN 50708 series, provided those devices and transformers contribute to increasing the proportion of renewable energy in the system or improve energy
- Commission Delegated Regulation (EU) 2023/2485 of 27 June 2023 amending Delegated Regulation (EU) 2021/2139 establishing additional technical screening criteria for determining the conditions under which certain economic activities qualify as contributing substantially to climate change mitigation or climate change adaptation and for determining whether those activities cause no significant harm to any of the other environmental objectives (Text with EEA relevance) Regulation · Grade B
Substantial contribution to climate change mitigation The activity manufactures, repairs, maintains, overhauls, retrofits, designs, repurposes or upgrades one of the following: Do no significant harm (DNSH) Climate change adaptation The activity complies with the criteria set out in Appendix A to this Annex. Sustainable use and protection of water and marine resources The activity complies with the criteria set out in Appendix B to this Annex. Transition to a circular economy The activity assesses the availability of and, where feasible, adopts techniques that support: Measures are in place to
- Commission Delegated Regulation (EU) 2023/2485 of 27 June 2023 amending Delegated Regulation (EU) 2021/2139 establishing additional technical screening criteria for determining the conditions under which certain economic activities qualify as contributing substantially to climate change mitigation or climate change adaptation and for determining whether those activities cause no significant harm to any of the other environmental objectives (Text with EEA relevance) Regulation · Grade B
installation of transmission and distribution transformers that comply with the Tier 2 (1 July 2021) requirements set out in Annex I to Commission Regulation (EU) No 548/2014 and, for medium power transformers with highest voltage for equipment not exceeding 36 kV, with AA0 level requirements on no-load losses set out in standard EN 50588-1*1. CEI EN 50588-1 Medium power transformers 50 Hz, with highest voltage for equipment not exceeding 36 kV.;
- Commission Implementing Regulation (EU) 2026/2133 of 18 September 2026 imposing a provisional safeguard measure with regard to imports of certain grain-oriented flat-rolled products of silicon-electrical steel Regulation · Grade B
Several interested parties claimed that the Union producers met neither the quantity nor the quality of Union users’ demand. Furthermore, the total capacity of the Union GOES industry would not meet the Union GOES consumption. Moreover, GOES produced by the Union industry would not meet the core loss and noise requirements required under Commission Regulation (EU) No 548/2014. Subsequently, the Union transformer industry would not be able to produce transformers meeting these requirements. Moreover, parties claimed that a measure would significantly increase GOES and SLC prices for the downstr
- Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance) Regulation · Grade B
Article 7 of Commission Regulation (EU) No 548/2014 requires the Commission to review that Regulation in the light of technological progress and present the results of this review to the Consultation Forum in 2017.
- Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance) Regulation · Grade B
The study confirmed that Regulation (EU) No 548/2014 has had a positive effect on the efficiency of power transformers being placed on the market, and found that available transformer models can fulfil minimum requirements set in Tier 1 (July 2015) without difficulties.
- Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance) Regulation · Grade B
Experience gained in implementing Regulation (EU) No 548/2014 has revealed the existence of national deviations in standard voltages in electricity distribution grids in certain Member States. These deviations justify different threshold voltage levels in the categorisation of transformers, and they inform what minimum energy performance requirements should be applicable. Therefore, the inclusion of a notification mechanism to provide publicity for specific situations in Member States is justified.
- Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance) Regulation · Grade B
Regulation (EU) No 548/2014 is amended as follows:
- Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance) Regulation · Grade B
The Annexes to Regulation (EU) No 548/2014 are amended as follows: Annex I is amended as follows: Annex II is replaced by the following: Annex III is amended as follows: in Annex IV, point (c) is amended as follows:
- Commission Notice The 2026 annual Union work programme for European standardisation C/2026/1695 Notice · Grade B
Public procurement documents (Action 43) Ref Title Reference European standards / European standardisation deliverables Specific objectives and policies for European standards / European standardisation deliverables 1 Artificial intelligence Regulation (EU) 2024/1689 laying down harmonised rules on artificial intelligence (Artificial Intelligence Act) Preparation of standardisation request to develop European standards and/or European standardisation deliverables in support of Article 40 of Regulation (EU) 2024/1689 (Artificial Intelligence Act), covering: (i) reporting and documentation proce
- Public notification from the European Commission 2021/C 475/01 Notice · Grade B
Article 3 of Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers provides that: If threshold voltages in electricity distribution networks deviate from the standard ones across the Union, Member States shall notify the Commission accordingly, so that a public notification can be made for the correct interpretation of Tables I.1, I.2, I.3a, I.3b, I.4, I.5, I.6, I.7, I.8 and I.9 in Annex I. Pursuant to this provision, the Czech Republic has notified to t
- Commission Notice The 2025 annual Union work programme for European standardisation C/2025/1818 Notice · Grade B
Consumer products safety (Action 78) Actions for the development and revision of European standards or European standardisation deliverables supporting the resilience of European industry Ref. Title Reference European standards / European standardisation deliverables Specific objectives and policies for European standards / European standardisation deliverables 1 Recycling critical raw materials from permanent magnets Regulation (EU) 2024/1252 establishing a framework for ensuring a secure and sustainable supply of critical raw materials Development of European standards for recycling permanen
- Commission Notice The 2024 annual Union work programme for European standardisation C/2024/1364 Notice · Grade B
Actions for the development and revision of European standards or European standardisation deliverables supporting the resilience of European industry Ref Title Reference European standards/European standardisation deliverables Specific objectives and policies for European standards/European standardisation deliverables 1 Recycling critical raw materials from permanent magnets COM/2023/160 final Proposal for a Regulation of the European Parliament and of the Council establishing a framework for ensuring a secure and sustainable supply of critical raw materials and amending Regulations (EU) 168