Commission Delegated Regulation (EU) 2026/331 of 13 February 2026 supplementing Regulation (EU) 2024/3110 of the European Parliament and of the Council by determining classes of performance in relation to the essential characteristic reaction to fire (Text with EEA relevance)
Grade B
mapped from publisher markup. A grade says how a document's structure was obtained, not how reliable the law is.
Address https://gelex.eu/eli/EU/regulation/2026/331@2026-02-13/en
THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Having regard to Regulation (EU) 2024/3110 of the European Parliament and of the Council of 27 November 2024 laying down harmonised rules for the marketing of construction products and repealing Regulation (EU) No 305/2011, and in particular Article 5(5), third subparagraph thereof,
Whereas:
(1) In order to enable manufacturers to declare sufficiently detailed classes of performance of products within the harmonised zone established pursuant to Article 11 of Regulation (EU) 2024/3110, it is necessary to establish classes of performance that are aligned to the latest technological and market developments.
(2) Classes of performance in relation to the essential characteristic reaction to fire were established by Commission Delegated Regulation (EU) 2016/364 on the basis of Regulation (EU) No 305/2011 of the European Parliament and of the Council. However, those classes of performance are not applicable under Regulation (EU) 2024/3110. Therefore, in order to keep the continuity of the system, the CPR Acquis Expert Group advised the Commission to establish the same classes of performance set out by Delegated Regulation (EU) 2016/364.
(3) The Commission should therefore determine the classes of performance to be used for the declaration of the essential characteristic reaction to fire,
HAS ADOPTED THIS REGULATION:
Article 1
The classes of performance in relation to the essential characteristic reaction to fire of products shall be those set out in the Annex.
Article 2
This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union.
This Regulation shall be binding in its entirety and directly applicable in all Member States. Done at Brussels, 13 February 2026. For the Commission The President Ursula von der Leyen
ANNEX
ANNEX A.
SYMBOLS For the purposes of this Annex, the following symbols apply: For all classes ΔΤ temperature rise Δm mass loss tf duration of flaming PCS gross calorific potential LFS lateral flame spread SMOGRA smoke growth rate For all classes except for classes related to electric cables FIGRA fire growth rate THR total heat release TSP total smoke production Fs flame spread For classes related to electric cables only HRRsm30, kW heat release rate averaged by a 30-s sliding average SPRsm60, m2/s smoke production rate averaged by a 60-s sliding average Peak HRR, kW maximum of HRRsm30 between test start and end of test, excluded contribution from ignition source Peak SPR, m2/s maximum of SPRsm60 between test start and end of test THR1200, MJ total heat release (HRRsm30) from test start until end of test, excluded contribution from ignition source TSP1200, m2 total smoke production (HRRsm60) from test start until end of test FIGRA, W/s fire growth rate index defined as the highest value of the quotient between HRRsm30 excluding the contribution of ignition source and time. Threshold values HRRsm30 = 3 kW and THR = 0,4 MJ FS flame spread (damaged length) H flame spread
B.
DEFINITIONS For the purposes of this Annex the following definitions apply:
(1) material means a single basic substance or uniformly dispersed mixture of substances;
(2) homogeneous product means a product consisting of a single material, having uniform density and composition throughout the product;
(3) non-homogeneous product means a product that does not satisfy the requirements of a homogeneous product and that is composed of one or more components, substantial and/or non-substantial;
(4) substantial component means a material that constitutes a significant part of a non-homogeneous product. A layer with a mass per unit area ≥ 1,0 kg/m2 or a thickness ≥ 1,0 mm is considered to be a substantial component;
(5) non-substantial component means a material that does not constitute a significant part of a non-homogeneous product. A layer with a mass per unit area < 1,0 kg/m2 and a thickness < 1,0 mm is considered to be a non- substantial component. Two or more non-substantial layers that are adjacent to each other, where there are no substantial components in between the layers, are considered as one non-substantial component and are classified in accordance with the criteria for a layer that is a non-substantial component;
(6) internal non-substantial component means a non-substantial component that is covered on both sides by at least one substantial component;
(7) external non-substantial component means a non-substantial component that is not covered on one side by a substantial component.
C.
CLASSES OF PERFORMANCE IN RELATION TO THE ESSENTIAL CHARACTERISTIC REACTION TO FIRE OF PRODUCTS
General
The relevant definitions, tests and performance criteria are fully described or referenced in the relevant harmonised technical specifications, European assessment documents, European reaction to fire classification standards and European testing standards.
1. Table 1 Products excluding floorings, linear pipe thermal insulation products, and electric cables Class Test method(s) Classification criteria Additional classification A1 Non-combustibility test; and ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (that is to say, no sustained flaming). Heat of combustion test PCS ≤ 2,0 MJkg-1; and PCS ≤ 2,0 MJkg-1; and PCS ≤ 1,4 MJm-2; and PCS ≤ 2,0 MJkg-1. A2 Non-combustibility test; or ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s. Heat of combustion test; and PCS ≤ 3,0 MJkg-1; and PCS ≤ 4,0 MJm-2; and PCS ≤ 4,0 MJm-2; and PCS ≤ 3,0 MJkg-1. Single burning item test). FIGRA0,2MJ ≤ 120 Ws-1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ. Smoke production; and Flaming droplets/particles. B Single burning item test; and FIGRA0,2MJ ≤ 120 Ws-1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ. Smoke production; and Flaming droplets/particles. Ignitability test: Exposure = 30 s. Fs ≤ 150 mm within 60 s. C Single burning item test; and FIGRA0,4MJ ≤ 250 Ws-1; and LFS < edge of specimen; and THR600s ≤ 15 MJ. Smoke production; and Flaming droplets/particles. Ignitability test: Exposure = 30 s. Fs ≤ 150 mm within 60 s. D Single burning item test; and FIGRA0,4MJ ≤ 750 Ws-1. Smoke production; and Flaming droplets/particles. Ignitability test: Exposure = 30 s. Fs ≤ 150 mm within 60 s. E Ignitability test: Exposure = 15 s. Fs ≤ 150 mm within 20 s. Flaming droplets/particles F Ignitability test: Exposure = 15 s. Fs > 150 mm within 20 s.
2. Table 2 Floorings Class Test method(s) Classification criteria Additional classification A1FL Non-combustibility test; and ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (that is to say, no sustained flaming). Heat of combustion test. PCS ≤ 2,0 MJkg-1; and PCS ≤ 2,0 MJkg-1; and PCS ≤ 1,4 MJm-2; and PCS ≤ 2,0 MJkg-1. A2FL Non-combustibility test; or ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s. Heat of combustion test; and PCS ≤ 3,0 MJkg-1; and PCS ≤ 4,0 MJm-2; and PCS ≤ 4,0 MJm-2; and PCS ≤ 3,0 MJkg-1. Determination of the burning behaviour using a radiant heat source test. Critical flux ≥ 8,0 kWm-2. Smoke production. BFL Determination of the burning behaviour using a radiant heat source test; and Critical flux ≥ 8,0 kWm-2. Smoke production. Ignitability test: Exposure = 15 s. Fs ≤ 150 mm within 20 s. CFL Determination of the burning behaviour using a radiant heat source test; and Critical flux ≥ 4,5 kWm-2. Smoke production. Ignitability test: Exposure = 15 s. Fs ≤ 150 mm within 20 s. DFL Determination of the burning behaviour using a radiant heat source test; and Critical flux ≥ 3,0 kWm-2. Smoke production. Ignitability test: Exposure = 15 s. Fs ≤ 150 mm within 20 s. EFL Ignitability test: Exposure = 15 s. Fs ≤ 150 mm within 20 s. FFL Ignitability test: Exposure = 15 s. Fs > 150 mm within 20 s.
3. Table 3 Linear pipe insulation products Class Test method(s) Classification criteria Additional classification A1L Non-combustibility test; and ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (that is to say, no sustained flaming). Heat of combustion test. PCS ≤ 2,0 MJkg-1; and PCS ≤ 2,0 MJkg-1; and PCS ≤ 1,4 MJm-2; and PCS ≤ 2,0 MJkg-1. A2L Non-combustibility test; or ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s. Heat of combustion test; and PCS ≤ 3,0 MJkg-1; and PCS ≤ 4,0 MJm-2; and PCS ≤ 4,0 MJm-2; and PCS ≤ 3,0 MJkg-1. Single burning item test. FIGRA0,2MJ ≤ 270 Ws-1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ. Smoke production; and Flaming droplets/particles. BL Single burning item test; and FIGRA0,2MJ ≤ 270 Ws-1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ. Smoke production; and Flaming droplets/particles. Ignitability test: Exposure = 30 s. Fs ≤ 150 mm within 60 s. CL Single burning item test; and FIGRA0,2MJ ≤ 460 Ws-1; and LFS < edge of specimen; and THR600s ≤ 15 MJ. Smoke production; and Flaming droplets/particles. Ignitability test: Exposure = 30 s. Fs ≤ 150 mm within 60 s. DL Single burning item test; and FIGRA0,4MJ ≤ 2 100 Ws-1; and THR600s ≤ 100 MJ. Smoke production; and Flaming droplets/particles. Ignitability test: Exposure = 30 s. Fs ≤ 150 mm within 60 s. EL Ignitability test: Exposure = 15 s. Fs ≤ 150 mm within 20 s. Flaming droplets/particles. FL Ignitability test: Exposure = 15 s. Fs > 150 mm within 20 s.
4. Table 4 Electric cables Class Test method(s) Classification criteria Additional classification Aca Heat of combustion test. PCS ≤ 2,0 MJkg-1. B1ca Burning behaviour and smoke production of bunched cable test (30 kW flame source); and FS ≤ 1,75 m; and THR1200s ≤ 10 MJ and Peak HRR ≤ 20 kW and FIGRA ≤ 120 Ws-1. Smoke production; and Flaming droplets/particles; and Acidity (pH and conductivity). Vertical flame spread of single cable test. H ≤ 425 mm. B2ca Burning behaviour and smoke production of bunched cable test (20,5 kW flame source); and FS ≤ 1,5 m; and THR1200s ≤ 15 MJ and Peak HRR ≤ 30 kW and FIGRA ≤ 150 Ws-1. Smoke production; and Flaming droplets/particles; and Acidity (pH and conductivity). Vertical flame spread of single cable test. H ≤ 425 mm. Cca Burning behaviour and smoke production of bunched cable test (20,5 kW flame source); and FS ≤ 2,0 m; and THR1200s ≤ 30 MJ; and Peak HRR ≤ 60 kW; and FIGRA ≤ 300 Ws-1. Smoke production; and Flaming droplets/particles; and Acidity (pH and conductivity). Vertical flame spread of single cable test. H ≤ 425 mm. Dca Burning behaviour and smoke production of bunched cable test (20,5 kW flame source); and THR1200s ≤ 70 MJ; and Peak HRR ≤ 400 kW; and FIGRA ≤ 1300 Ws-1. Smoke production; and Flaming droplets/particles; and Acidity (pH and conductivity). Vertical flame spread of single cable test. H ≤ 425 mm. Eca Vertical flame spread of single cable test. H ≤ 425 mm. Fca Vertical flame spread of single cable test. H > 425 mm.